Two possible reasons:
1. Tamper plunger is not being held back by the screw on the upper left of the front of the device. Make sure the unit is mounted and the top left tamper screw is installed. Check That the security plunger is engaging the security micro switch on the back of the PCB.
2. Set to auto rearm(non-extended bypass) and the magnet on the frame not aligned properly. Isolate the device by using a jumper to simulate the door closure in inputs 5 and 6. If your device works, then check you magnet switch continuity. The magnetic switch is a closed contact when the door is closed and opens when the door is opened. These two wires should be connected to terminals 5 & 6.
With more outdoor areas needing to be secured, businesses and property owners are looking for…
Detex Corporation is proud to announce that it has received the Outstanding Manufacturing Mentor Award…
There are four basic types of standard hinges: full mortise, half mortise, full surface and…
New Braunfels, TX — Detex Corporation is honored to announce its nomination for the Outstanding…
Regular door hardware maintenance is essential for ensuring safety, security, and compliance with building codes.…
If there are wires landed on the J2 fire loop, check the LED2. If it…