Two possible reasons:
1. Tamper plunger is not being held back by the screw on the upper left of the front of the device. Make sure the unit is mounted and the top left tamper screw is installed. Check That the security plunger is engaging the security micro switch on the back of the PCB.
2. Set to auto rearm(non-extended bypass) and the magnet on the frame not aligned properly. Isolate the device by using a jumper to simulate the door closure in inputs 5 and 6. If your device works, then check you magnet switch continuity. The magnetic switch is a closed contact when the door is closed and opens when the door is opened. These two wires should be connected to terminals 5 & 6.
If there are wires landed on the J2 fire loop, check the LED2. If it…
The arm may have been installed wrong. To reinstall the arm, remove from spindle and…
Refer to the installation instructions and follow the instructions
The key is turned to the armed position, but the device does not sound when…
The likely causes are that either: - Your door contact is not activating when the…